Ventilation Rate Calculator
Check the whole-dwelling ventilation rate and per-room extract against UK Approved Document F or international ASHRAE 62.2, with air-change conversion — for damp, mould and Decent Homes work.
Approved Document FASHRAE 62.2Whole-dwelling ratePDF reportFree to use
Approved Document F (England, 2021).
Whole-dwelling rate
3
135+
Required whole-dwelling rate
31 l/s
Governed by number of bedrooms. Bedrooms: 31 l/s · floor area: 27 l/s.
Room extract check
Part F: 30 l/s adjacent to the hob. ASHRAE 62.2: 100 cfm (47 l/s) intermittent.
Anemometer reading at the fan, or the fan's rated duty.
Meets minimum extract
Min 30 l/s · 4.5 ACH · purge 0.50 m²
Approved Document F — key rates
| Whole-dwelling (greater of the two) | |
| 1 / 2 / 3 / 4 / 5 bed | 19 / 25 / 31 / 38 / 44 l/s |
| Floor-area floor | 0.3 l/s per m² |
| Intermittent extract (minimum) | |
| Kitchen (hob / elsewhere) | 30 / 60 l/s |
| Utility | 30 l/s |
| Bathroom | 15 l/s |
| WC / cloakroom | 6 l/s |
Figures from Approved Document F (England, 2021). Continuous mechanical systems use the separate continuous rates. Verify against the current edition.
Using this correctly
Frequently Asked Questions
Disclaimer: This calculator applies the indicative ventilation rates in Approved Document F (England, 2021) for screening and condition reporting. It does not assess continuous mechanical systems in full, ductwork sizing, commissioning or air-tightness interactions, and figures may differ in other nations and countries. Always verify against the current Approved Document F (or applicable standard) and the system manufacturer's commissioning data.